SUSTAINABLE CLIMATE SOLUTION
cooling, heating and AC for distribution center
#gonatrefs
FACTS
End-user: Lidl Ireland
Segment: Distribution Center
Contractor: RSL Ireland
Background: New energy-optimised distribution centre
Products: 5 SteelXL with heat recovery and 2 chiller modules
Background
- Identical racks for easy operation and
maintenance - Multiple racks to provide redundancy and
resilience to the plant - Direct expansion system for LT and MT
- Chillers for HT and AC
- Wanted a sustainable and energy efficient solution
with natural refrigerants
Solution
- 3 identical racks SteelXL 6+3x4
> 183 kW @ -38°C
> 475 kW @ -8°C - Drive on two first MT and LT compressors for load flexibility and redundancy
- 2 racks for chilled glycol for HT and AC SteelX 5x0 - > 335 kW @ 0°C
- 2 dx chillers modules for each rack for part load and redundancy
A sustainable and energy efficient solution combining cooling, freezing, air-con and heating in one solution